| ©2026 Respective owners and brand holders. This table has been carefully researched and generated by ComXpert International CC (//www.comx-computers.co.za), however, errors and omissions may occur. Only references to South Africa apply. All products are sourced in South Africa from the official suppliers and the warranty is that of the local supplier. E&OE. This table and our site's content may be used on condition that this notice and link remains intact and unaltered. |
Specifications |
| Product Code | G35T30KHS |
| Output |
| Output Power Capacity | 24 kW / 30 kVA |
| Max Configurable Power | 24 kW / 30 kVA |
| Nominal Output Voltage | 400V 3PH |
| Output Voltage Note | Configurable for 380 : 400 or 415 V 3 Phase nominal output voltage |
| Efficiency at Full Load | 0.958 |
| Output Voltage Distortion | Less than 5% |
| Output Frequency (sync to mains) | 47 - 53 Hz for 50 Hz nominal |
| Other Output Voltages | 380415 |
| Crest Factor | Unlimited |
| Waveform Type | Sine wave |
| Output Connections | (1) Hard Wire 4-wire (3PH + G) |
| (1) Hard Wire 5-wire (3PH + N + G) | (1) Screw Terminals |
| Output Voltage Tolerance | +/-1% static and +/- 5% at 100% load step |
| Output Voltage THD | < 2% for 0 to 100% linear load and < 5% for full n |
| Overload Operation | 10 minutes @ 125% and 60 seconds @ 150% |
| Efficiency at Half Load | 0.95 |
| Required Output Current Protection | 50A |
| Bypass | Built-in Maintenance Bypass, Built-in Static Bypass |
| Input |
| Nominal Input Voltage | 400V 3PH |
| Input Frequency | 40 - 70 Hz (auto sensing) |
| Input Connections | Hard Wire 5-wire (3PH + N + G) |
| Input voltage range for main operations | 304 - 477V |
| Input voltage adjustable range for mains operation | 340 - 460 (400V)V |
| Other Input Voltages | 380415 |
| Maximum Input Current | 43A |
| Input Breaker Capacity | 50.0 A |
| Input Total Harmonic Distortion | Less than 5% for full load |
| Type of Input Protection Required | 3-pole breaker |
| Batteries & Runtime |
| Battery Type | No internal battery supplied with UPS - can be used with external third party batteries or SYBTH4 |
| Nominal Battery Voltage | +/-192 V (split battery referenced to neutral) |
| End of Discharge Battery Voltage | +/-154 V |
| Overload Operation | 10 minutes @ 125% and 60 seconds @ 150% |
| Extended Run Options | MGE Galaxy 3500 30kVA 400V, Start-Up 5X8 |
| Communications & Management |
| Interface Port(s) | DB-9 RS-232, G35T |
| Pre-Installed SmartSlot Cards | AP9631 |
| Control panel | Multi-function LCD status and control console |
| Audible Alarm | Alarm when on battery : distinctive low battery alarm : configurable delays |
| Emergency Power Off (EPO) | Yes |
| Physical |
| Maximum Height | 1491.00 mm |
| Maximum Width | 523.00 mm |
| Maximum Depth | 838.00 mm |
| Net Weight | 294.00 KG |
| Shipping Weight | 325.00 KG |
| Shipping Height | 1643.00 mm |
| Shipping Width | 650.00 mm |
| Shipping Depth | 1062.00 mm |
| Environmental |
| Operating Environment | 0 - 40 °C |
| Operating Relative Humidity | 0 - 95% |
| Operating Elevation | 0-999.9 meters |
| Storage Temperature | -15 - 45 °C |
| Storage Relative Humidity | 0 - 95% |
| Storage Elevation | 0-15000 meters |
| Audible noise at 1 meter from surface of unit | 55.00 dBA |
| Online Thermal Dissipation | 3685.00 BTU/hr |
| Protection Class | IP 51 |
| Conformance |
| Regulatory Approvals | CE, EN 50091-2, EN/IEC 62040-3, EN/IEC 62040-1-1, IEC 61000-3-2, IEC 61000-3-3, ISO 14001, ISO 9001, VFI-SS-111 |